Chilled Water Pressurization Unit
The unit shall consist of:
1 Package assembly of pressurization pump, buffer tank(s) complete with control panel.
Chilled water pressurization unit shall have its control panel connected to the Building Management System to indicate its operational status and whether it is in fault thru a volt free contact (VFC) from the control panel to DDC.
A graphical representation of the plant will be produced with all set points, alarms and time schedules displayed with simple mouse clicks. Access to the graphic will be through a system of site plans, plant rooms and systems.
All values are to be historically recorded at controller level so that locally any laptop or Portable operator’s terminal may retrieve the data as well as the network BMS Supervisor.
Chilled Water Vacuum Deaerator
The unit shall consist of:
Package assembly of pump, vacuum vessel, sensor and valves complete with control panel.
Chilled water vacuum deaerator unit shall have its control panel connected to the Building Management System to indicate its operational status and whether it is in fault through volt free contact (VFC) from vacuum deaerator control panel to DDC.
A graphical representation of the plant will be produced with all set points, alarms and time schedules displayed with simple mouse clicks. Access to the graphic will be through a system of site plans, plant rooms and systems.